Medical centre fit out: unisex toilets for 20 staff (NSW)

  • Building: Class 5 medical centre fit out within an existing shopping centre

  • Location: South west Sydney, NSW

  • NCC edition: NCC 2022 (Amendment 2), Volume One

  • Area of NCC requirements: F4P1 personal hygiene facilities and D1P1 access; F4D4, F4D5(3) and AS 1428.1

  • Raised by: The certifier, in the complying development certificate checklist

  • Year: 2026

The challenge

The fit out has three single occupancy toilet rooms: an accessible unisex facility, a unisex WC and a staff WC. With 20 staff, F4D4 calls for separate male and female facilities, as unisex facilities are only permitted outright where 10 or fewer people are employed. Because a single toilet counts as a bank of sanitary facilities, F4D5(3) also technically required the staff WC itself to be an ambulant compartment.

The performance solution

Expert judgement and comparison with the Deemed to Satisfy Provisions resolved both departures:

  • Under F4D3, an accessible unisex facility counts once for each sex. Read with F4D4(3), that one facility covers 10 male and 10 female staff on a unisex basis, so the other two rooms are additional provision.

  • Patients at a medical centre are often helped by a parent or carer of the other sex. Single occupancy rooms allow that in privacy, which a multi compartment single sex facility does not.

  • The all gender provisions introduced in NCC 2025 were used as a supporting argument. Each room already has one pan and one basin, opens off a common hall and is to be signed "all gender".

  • Each room has a full height enclosure, a privacy lock that releases from outside, its own basin with soap and hand drying, and mechanical ventilation to AS 1668.2.

  • The unisex WC is converted to an AS 1428.1 ambulant compartment, 900 mm to 920 mm wide, with an amended 1:20 detail to the certifier. Staff therefore have both an ambulant and an accessible toilet on the same level.

  • The staff WC gets grabrails at the pan and a self closing door that opens outward, slides or has removable hinges, in line with F4D8.

Outcome

Report prepared in November 2026 and successfully accepted by the certifier.

Lesson for designers

Small tenancies often fail on clause counting rather than design. The rule that an accessible unisex toilet counts once for each sex is frequently the difference between approval and a costly redesign.